| Input |
RTD, type Pt100 |
| Sensor Temperature Ranges |
See Box1 code for standard ranges. Field re-scalable between -200 ºC to 600 ºC
or -50 ºC to 200 ºC, depending on model. |
| Outputs |
4-20 mA loop powered, 2-wire, linear to temperature
0-5 Vdc, 1-5 Vdc, 0-10 Vdc all 3-wire, linear to temperature |
| Minimum Input Impedance |
1000 Ohm (of measuring device, for voltage output) |
| Power Supply |
12-32 VDC, polarity protected |
| Supply Effect |
0.001 % / V |
| Accuracy |
± ( .25 ºC + 0.40 % of span ) with one-point calibration 1.
± ( .10 ºC + 0.10 % of calibrated span ) with two-point calibration 2. |
| Maximum Loop Resistance |
[ ( Vsupply – 7 ) * 40 ] ohms ( for 4-20 mA output only ) |
| Sensor Open Circuit |
Upscale 24 mA or Downscale 2.5 mA ( for 4-20 mA output only ) |
| Warmup |
30 seconds |
| RFI Effect |
1 % or less typical |
| Isolation |
500 Vdc Input / Output |
| Temp. Effects |
± 0.001 % of Span / ºC |
| Long Term Drift |
≤ 0.1 % FS / Year |