| Sensing Element | RTD, Type Pt100 DIN/EN 60751 Class A |
| Sensor Current | < 0.25 mA |
| Sensor Temperature Ranges | See Box1 code for standard ranges. Field re-scalable between or -50 ºC to 200 ºC or -200 ºC to 600 ºC depending on model selected. |
| Outputs | 4-20 mA loop powered, 2-wire, linear to temperature 0-5 VDC, 1-5 VDC, 0-10 VDC all 3-wire, linear to temperature |
| Minimum Input Impedance | 1000 Ohm ( of measuring device, for voltage output ) |
| Power Supply | 9-30 VDC, polarity protected ( 4-20 mA output ) 12-30 VDC, polarity protected ( Voltage output ) |
| Supply Effect | 0.001%/V |
| Maximum Loop Resistance | [ ( Vsupply – 7 V ) /20mA ] ohms ( for 4-20mA output only ) |
| Maximum Current Draw | 10 mA ( Voltage output only ) |
| Accuracy | ± ( .25 ºC + 0.40% of span ) with one-point calibration1. ± ( .10 ºC + 0.10% of calibrated span ) with two-point calibration 2. |
| Sensor Open Circuit | Upscale 24 mA or Downscale 2.5 mA ( for 4-20 mA output only ) |
| Warm-up | 30 seconds |
| RFI Effect | 1% or less typical |
| Isolation | 500 VDC , sensor housing to all output Pins |
| Temp. Effects | ± 0.001% of Span / ºC deviation from 25 ºC |
| Long Term Drift | ≤ 0.1% FS / Year |