4-20mA. Ranges available between -184°F to +68°F (-120°C to +20°C)
Model AMT Dewpoint Transmitter is a two wire 4-20mA loop powered transmitter, used for continuous measurement of moisture in dry process gases or dry compressed air, which will output a linear 4-20mA signal corresponding to the dewpoint temperature. The Model AMT transmitter can also be factory configured to output a 4-20mA linear signal for any other moisture unit e.g. ppm(v), ppm(w), g/m3, lb/MMSCF etc.
The Ultra High Capacitance sensing element is long lasting and offers excellent
sensitivity, repeatability and response speed. Each unit is supplied with a Certificate of Calibration, traceable to International Humidity Standards, validating accuracy better than ±3.60F (±20C) dewpoint.
The transmitter also incorporates an Automatic Calibration (AUTOCAL) feature, which allows the user to carry out a field calibration / span check. The AUTOCAL feature is operated by two small button switches built within the transmitter enclosure. To avoid tamper, the switches are locked in normal use and can only be activated by following a specific routine from the manual.
The integral RISC microprocessor circuitry of the Model AMT transmitter allows high resolution with advanced self diagnostics for fault conditions. It also enables periodic re-calibration of the moisture sensor, storing calibration data within the fully self contained unit. Loop powered by a 7V to 28V dc source, the Model AMT transmitter will provide a linear 4-20mA signal over the chosen range.
The mechanics of the Model AMT transmitter have been designed to cope with extreme environmental conditions. The rugged stainless steel construction offers protection to NEMA4X (IP66), with the transmitter electrical connections made via a secure industrial connector.
Model AMT transmitter can withstand 5,076PSIA (350barA) maximum pressure and by employing a low resistance cable, the transmitter can be located at significant distances, in excess of 3300 feet (1km), from the control room.
Designed with the operator in mind for reliable and accurate measurements, the Model AMT transmitter is extremely easy to install and operate, requiring little or no maintenance.
Note: The Model AMT is not suitable for Ammonia (NH3), Chlorine (CI) and Hydrogen Chloride (HCI). SF6 can be monitored with no effect to the sensor element. Sulphur Dioxide (SO2) can be monitored if the moisture content is low, less than 100ppm(v).
The Model AMT transmitter is supplied with a Certificate of Calibration, an instruction manual and 2m connecting cable.
4-20mA Loop Powered Transmitter
TRANSMITTER TYPE: 2 Wire, 4-20mA Loop Powered Transmitter
OUTPUT SIGNAL: 4 to 20mA Linear
OPERATING VOLTAGE: 7V – 28V dc. Reverse polarity protected.
MAXIMUM SERIES RESISTANCE: = {40 x (Supply Voltage – 7)} ohms
SENSING ELEMENT: Ultra High Capacitance – Aluminium Oxide Type
RANGES: See How to Order Below
AUTOCAL: Field calibration / Span check facility. Activated and operated via two button switches on the Transmitter body. Locked in normal operating mode to avoid tamper.
FACTORY CALIBRATION: Supplied with Certificate of Calibration traceable to NIST / NPL
ACCURACY: Better than ±3.6°F (±2°C) dewpoint (NIST / NPL traceable for range -130°F to +68°F)
TEMPERATURE COEFFICIENT: Temperature compensated for operating range.
REPEATABILITY: Better than ±0.54°F dewpoint
OPERATING TEMPERATURE: -4°F to +140°F (-20°C to +60°C)
STORAGE TEMPERATURE: -4°F to +158°F (-20°C to +70°C)
OPERATING PRESSURE: From 0.145PSIA (0.01 barA) to Maximum 5,076PSIA (350barA)
OPERATING HUMIDITY (External): Maximum – 95% RH Non-condensing
SAMPLE FLOW RATE: Flow independent but ideally 2 to 5 litres per minute. Max: 25 litres/min.
CABLE TERMINATIONS: NEMA4X (IP66) rated, size C, DIN EN 175301 connector at the Transmitter and other end terminated with bootlace ferrules.
CABLE: Supplied with 6.6 feet standard cable. Nominal diameter 0.13 inches (3.3mm), 92ohms/km at 68°F (20°C)
ELECTROMAGNETIC COMPATIBILITY (EMC): Complies BS EN 61326-1
WARM UP TIME: 10 seconds
FAULT CONDITIONS:
Open Circuit : Output drives to 20.50mA
Short Circuit : Output drives to 20.75mA
ISOLATION: Sensing Element connected to the 4-20mA loop but isolated from Transmitter body.
TRANSMITTER ENCLOSURE: 316 Stainless steel body with size C, DIN EN 175301 connector.
SENSOR PROTECTION: 316 Sintered stainless steel filter – 50 micron
PROBE MATERIAL (WETTED PARTS): 316 Stainless Steel
WEATHERPROOF CLASSIFICATION: NEMA4X (IP66) when connector mated to transmitter.
MECHANICAL CONNECTION: 3/4” UNF (16tpi) with integral Viton “O” ring seal.
MECHANICAL WARRANTY: 24 months in case of faulty workmanship and defective parts.
CALIBRATION WARRANTY: 12 months.
ACCESSORIES INCLUDED: Standard 2 meter connecting cable.
The AMT Transmitter can be paired with the Model DS1200 if a Display is required. Click here for more details.
Range Code | Range |
RDF: | -112°F to -4°F (-80°C to -20°C) dewpoint resolution 0.1°F / °C |
SRF: | -166°F to -4°F (-110°C to -20°C) dewpoint resolution 0.1°F / °C |
GYF: | -112°F to +32°F (-80°C to 0°C) dewpoint resolution 0.1°F / °C |
PLF: | -148°F to +32°F (-100°C to 0°C) dewpoint resolution 0.1°F / °C |
BLF: | -112°F to 68°F (-80°C to +20°C) dewpoint resolution 0.1°F / °C |
SDF: | -148°F to +68°F (-100°C to +20°C) dewpoint resolution 0.1°F / °C |
SSRF: | -184°F to +68°F (-120°C to +20°C) dewpoint resolution 0.1°F / °C |
LDF: | -184°F to +68°F (-120°C to +20°C) dewpoint resolution 0.1°F / °C |
SHDF: | -85°F to +32°F (-65°C to 0°C) dewpoint resolution 0.1°F / °C |
HDF: | -85°F to +68°F (-65°C to +20°C) dewpoint resolution 0.1°F / °C |
RDC: | -80°C to -20°C (-112°F to -4°F) dewpoint resolution 0.1°F / °C |
SRC: | -110°C to -20°C (-166°F to -4°F) dewpoint resolution 0.1°F / °C |
GYC: | -80°C to 0°C (-112°F to 32°F) dewpoint resolution 0.1°F / °C |
PLC: | -100°C to 0°C (-148°F to 32°F) dewpoint resolution 0.1°F / °C |
BLC: | -80°C to +20°C (-112°F to 68°F) dewpoint resolution 0.1°F / °C |
SDC: | -100°C to +20°C (-148°F to 68°F) dewpoint resolution 0.1°F / °C |
SSRC: | -120°C to -20°C (-184°F to -4°F) dewpoint resolution 0.1°F / °C |
LDC: | -120°C to +20°C (-184°F to 68°F) dewpoint resolution 0.1°F / °C |
SHDC: | -65°C to 0°C (-85°F to 32°F) dewpoint resolution 0.1°F / °C |
HDC: | -65°C to +20°C (-85°F to 68°F) dewpoint resolution 0.1°F / °C |
GYP: | 1 to 6000 ppm(v) resolution = 2ppm |
SP: | 1 to 1000 ppm(v) resolution = 1ppm |
MP: | 0.1 to 100.0 ppm(v) resolution = 0.1ppm |
LP: | 0.01 to 10.00 ppm(v) resolution = 0.01ppm |
PB: | 1 to 1000 ppb(v) resolution = 1ppb |
HG: | 0.01 to 10.00 g/m3 resolution = 0.01g/m3 |
LG: | 0.001 to 1.000 g/m3 resolution = 0.001g/m3 |
LLB: | 0.1 to 10.0 lbs/MMSCF resolution 0.01 lbs/MMSCF |
SLB: | 0.1 to 25.0 lbs/MMSCF resolution 0.01 lbs/MMSCF |
HLB: | 0.1 to 50.0 lbs/MMSCF resolution 0.01 lbs/MMSCF |
VHLB: | 0.1 to 300.0 lbs/MMSCF resolution 0.01 lbs/MMSCF |
4-20mA. Ranges available between -184°F to +68°F (-120°C to +20°C)
Model AMT Dewpoint Transmitter is a two wire 4-20mA loop powered transmitter, used for continuous measurement of moisture in dry process gases or dry compressed air, which will output a linear 4-20mA signal corresponding to the dewpoint temperature. The Model AMT transmitter can also be factory configured to output a 4-20mA linear signal for any other moisture unit e.g. ppm(v), ppm(w), g/m3, lb/MMSCF etc.
The Ultra High Capacitance sensing element is long lasting and offers excellent
sensitivity, repeatability and response speed. Each unit is supplied with a Certificate of Calibration, traceable to International Humidity Standards, validating accuracy better than ±3.60F (±20C) dewpoint.
The transmitter also incorporates an Automatic Calibration (AUTOCAL) feature, which allows the user to carry out a field calibration / span check. The AUTOCAL feature is operated by two small button switches built within the transmitter enclosure. To avoid tamper, the switches are locked in normal use and can only be activated by following a specific routine from the manual.
The integral RISC microprocessor circuitry of the Model AMT transmitter allows high resolution with advanced self diagnostics for fault conditions. It also enables periodic re-calibration of the moisture sensor, storing calibration data within the fully self contained unit. Loop powered by a 7V to 28V dc source, the Model AMT transmitter will provide a linear 4-20mA signal over the chosen range.
The mechanics of the Model AMT transmitter have been designed to cope with extreme environmental conditions. The rugged stainless steel construction offers protection to NEMA4X (IP66), with the transmitter electrical connections made via a secure industrial connector.
Model AMT transmitter can withstand 5,076PSIA (350barA) maximum pressure and by employing a low resistance cable, the transmitter can be located at significant distances, in excess of 3300 feet (1km), from the control room.
Designed with the operator in mind for reliable and accurate measurements, the Model AMT transmitter is extremely easy to install and operate, requiring little or no maintenance.
Note: The Model AMT is not suitable for Ammonia (NH3), Chlorine (CI) and Hydrogen Chloride (HCI). SF6 can be monitored with no effect to the sensor element. Sulphur Dioxide (SO2) can be monitored if the moisture content is low, less than 100ppm(v).
The Model AMT transmitter is supplied with a Certificate of Calibration, an instruction manual and 2m connecting cable.
4-20mA Loop Powered Transmitter
TRANSMITTER TYPE: 2 Wire, 4-20mA Loop Powered Transmitter
OUTPUT SIGNAL: 4 to 20mA Linear
OPERATING VOLTAGE: 7V – 28V dc. Reverse polarity protected.
MAXIMUM SERIES RESISTANCE: = {40 x (Supply Voltage – 7)} ohms
SENSING ELEMENT: Ultra High Capacitance – Aluminium Oxide Type
RANGES: See How to Order Below
AUTOCAL: Field calibration / Span check facility. Activated and operated via two button switches on the Transmitter body. Locked in normal operating mode to avoid tamper.
FACTORY CALIBRATION: Supplied with Certificate of Calibration traceable to NIST / NPL
ACCURACY: Better than ±3.6°F (±2°C) dewpoint (NIST / NPL traceable for range -130°F to +68°F)
TEMPERATURE COEFFICIENT: Temperature compensated for operating range.
REPEATABILITY: Better than ±0.54°F dewpoint
OPERATING TEMPERATURE: -4°F to +140°F (-20°C to +60°C)
STORAGE TEMPERATURE: -4°F to +158°F (-20°C to +70°C)
OPERATING PRESSURE: From 0.145PSIA (0.01 barA) to Maximum 5,076PSIA (350barA)
OPERATING HUMIDITY (External): Maximum – 95% RH Non-condensing
SAMPLE FLOW RATE: Flow independent but ideally 2 to 5 litres per minute. Max: 25 litres/min.
CABLE TERMINATIONS: NEMA4X (IP66) rated, size C, DIN EN 175301 connector at the Transmitter and other end terminated with bootlace ferrules.
CABLE: Supplied with 6.6 feet standard cable. Nominal diameter 0.13 inches (3.3mm), 92ohms/km at 68°F (20°C)
ELECTROMAGNETIC COMPATIBILITY (EMC): Complies BS EN 61326-1
WARM UP TIME: 10 seconds
FAULT CONDITIONS:
Open Circuit : Output drives to 20.50mA
Short Circuit : Output drives to 20.75mA
ISOLATION: Sensing Element connected to the 4-20mA loop but isolated from Transmitter body.
TRANSMITTER ENCLOSURE: 316 Stainless steel body with size C, DIN EN 175301 connector.
SENSOR PROTECTION: 316 Sintered stainless steel filter – 50 micron
PROBE MATERIAL (WETTED PARTS): 316 Stainless Steel
WEATHERPROOF CLASSIFICATION: NEMA4X (IP66) when connector mated to transmitter.
MECHANICAL CONNECTION: 3/4” UNF (16tpi) with integral Viton “O” ring seal.
MECHANICAL WARRANTY: 24 months in case of faulty workmanship and defective parts.
CALIBRATION WARRANTY: 12 months.
ACCESSORIES INCLUDED: Standard 2 meter connecting cable.
The AMT Transmitter can be paired with the Model DS1200 if a Display is required. Click here for more details.
Range Code | Range |
RDF: | -112°F to -4°F (-80°C to -20°C) dewpoint resolution 0.1°F / °C |
SRF: | -166°F to -4°F (-110°C to -20°C) dewpoint resolution 0.1°F / °C |
GYF: | -112°F to +32°F (-80°C to 0°C) dewpoint resolution 0.1°F / °C |
PLF: | -148°F to +32°F (-100°C to 0°C) dewpoint resolution 0.1°F / °C |
BLF: | -112°F to 68°F (-80°C to +20°C) dewpoint resolution 0.1°F / °C |
SDF: | -148°F to +68°F (-100°C to +20°C) dewpoint resolution 0.1°F / °C |
SSRF: | -184°F to +68°F (-120°C to +20°C) dewpoint resolution 0.1°F / °C |
LDF: | -184°F to +68°F (-120°C to +20°C) dewpoint resolution 0.1°F / °C |
SHDF: | -85°F to +32°F (-65°C to 0°C) dewpoint resolution 0.1°F / °C |
HDF: | -85°F to +68°F (-65°C to +20°C) dewpoint resolution 0.1°F / °C |
RDC: | -80°C to -20°C (-112°F to -4°F) dewpoint resolution 0.1°F / °C |
SRC: | -110°C to -20°C (-166°F to -4°F) dewpoint resolution 0.1°F / °C |
GYC: | -80°C to 0°C (-112°F to 32°F) dewpoint resolution 0.1°F / °C |
PLC: | -100°C to 0°C (-148°F to 32°F) dewpoint resolution 0.1°F / °C |
BLC: | -80°C to +20°C (-112°F to 68°F) dewpoint resolution 0.1°F / °C |
SDC: | -100°C to +20°C (-148°F to 68°F) dewpoint resolution 0.1°F / °C |
SSRC: | -120°C to -20°C (-184°F to -4°F) dewpoint resolution 0.1°F / °C |
LDC: | -120°C to +20°C (-184°F to 68°F) dewpoint resolution 0.1°F / °C |
SHDC: | -65°C to 0°C (-85°F to 32°F) dewpoint resolution 0.1°F / °C |
HDC: | -65°C to +20°C (-85°F to 68°F) dewpoint resolution 0.1°F / °C |
GYP: | 1 to 6000 ppm(v) resolution = 2ppm |
SP: | 1 to 1000 ppm(v) resolution = 1ppm |
MP: | 0.1 to 100.0 ppm(v) resolution = 0.1ppm |
LP: | 0.01 to 10.00 ppm(v) resolution = 0.01ppm |
PB: | 1 to 1000 ppb(v) resolution = 1ppb |
HG: | 0.01 to 10.00 g/m3 resolution = 0.01g/m3 |
LG: | 0.001 to 1.000 g/m3 resolution = 0.001g/m3 |
LLB: | 0.1 to 10.0 lbs/MMSCF resolution 0.01 lbs/MMSCF |
SLB: | 0.1 to 25.0 lbs/MMSCF resolution 0.01 lbs/MMSCF |