Combustible Gas Detector system eliminates the need for frequent response checks with ATi’s pioneering AutoTest. This transmitter performs an automatic test using self-generated gas on the sensing element every 24 hours with the world’s only self-testing AutoTest gas module for complete peace of mind, allowing for safer and more confident monitoring.
The A12-17 combustible gas sensors are made up of two matched sensing elements, one active and one passive. Both are electrically heated and form two legs of a Wheatstone bridge circuit. When combustible gas contacts the sensor, the active element catalyzes the oxidation of gas, heating the active element and changing its resistance. The passive element remains unchanged, resulting in a change in the bridge circuit that is proportional to the gas concentration. As long as the active element remains in good condition, the gas sensor will respond rapidly to the presence of combustible gas.
The Auto-Test gas sensor is a combination of a gas sensor and an electrochemical hydrogen gas generator integrated into an explosion-proof stainless steel housing. When activated by the electronic transmitter, the generator produces hydrogen that diffuses to the gas sensor through the flame arrestor protecting the sensor. If the gas sensor responds properly, the A12-17 Combustible Gas Transmitter will show a “Pass” indication. Should the sensor not respond properly, an “Auto Test Fail” message will activate at the gas transmitter and the 4-20 mA output from the transmitter will drop to 3 mA, providing for remote fault indication.
Combustible Gas Detectors are used in a wide variety of industrial plants to detect gas leakage or buildup before it reaches explosive levels. These detectors rely on thermal oxidation of any combustible gas or vapor on the surface of a heated catalyst. In other words, they simply burn the gas and measure the heat released in the combustion process.
While this type of sensor is generally stable and reliable, it is also subject to poisoning by silicon vapor, lead compounds, and other environmental contaminants. To detect loss of sensitivity, most users test combustible sensors either weekly or biweekly to ensure response. The procedure is simple, but requires manpower to perform the test.
ATI’s Auto-Test Combustible Gas Transmitter eliminates the need for frequent response checks. This transmitter performs an automatic gas test on the sensing element every 24 hours. The result is a combustible gas detector system with a level of reliability beyond that of any other system available. This daily sensor response verification is as close to a fail-safe detection system as you can find, with the added benefit of greatly reduced manual testing.
Combustible gas sensors are made up of two matched sensing elements, one active and one passive. Both are electrically heated and form two legs of a Wheatstone bridge circuit. When combustible gas contacts the sensor, the active element catalyzes the oxidation of gas, heating the active element and changing its resistance.
The passive element remains unchanged, resulting in a change in the bridge circuit that is proportional to the gas concentration. As long as the active element remains in good condition, the sensor will respond rapidly to the presence of combustible gas.
The Auto-Test sensor is actually a combination of a gas sensor and an electrochemical hydrogen gas generator integrated into an explosion-proof stainless steel housing.
When activated by the electronic transmitter, the generator produces hydrogen that diffuses to the gas sensor through the flame arrestor protecting the sensor. If the sensor responds properly, the combustible gas detector transmitter will show a “Pass” indication. Should the sensor not respond properly, an “Auto Test Fail” message will activate at the transmitter and the 4-20 mA output from the transmitter will drop to 3 mA, providing for remote fault indication.
Model A12-17 | – | DDD | – | E | – | F |
Code the measurement range using a 4-digit number. The standard range for a combustible gas system is 0-100% LEL, so the code is normally 0100. However, systems used for hydrogen are sometimes displayed in %, with a range of 0-4 percent (code 0004). If a range other than 0-100% LEL or 0-4% is required, consult factory for availability.
3 – %
4 – % LEL
1 – Sensor without Auto-Test
2 – Sensor with Auto-Test
3 – Remote sensor with junction box
4 – Remote sensor with junction box and Auto-Test
00-0261 Splash guard/remote calibration adapter for standard sensor
00-0258 Calibration adapter for standard sensor
45-0081 Splash guard for Auto-Test sensor (required for Auto-Test sensor)
Gas Type | Calibrated for methane unless otherwise specified |
Range | 0-100% LEL |
Response Time | (T90) 10 seconds |
Accuracy | Generally +5% of value, but limited by available calibration gas accuracy. |
Electronic Repeatability | +1% |
Electronic Linearity | +0.5% |
Zero Drift | Less than 2% full scale per month |
Span Drift | Less than 3% per month |
Output | Powered 4-20 mA, 1000 ohms max at 24 VDC |
Power | 12-30 VDC, 125 mA maximum |
Enclosure | Explosion-proof, Class 1, Div 1, Groups B,C, & D |
Sensor | 316 stainless steel |
Sensor Auto-Test | Hydrogen gas generator integral to gas sensor housing |
Control | 4 magnetic switches on front of transmitter |
Operating Temp | -40 ̊F to +70 ̊C |
Weight | 4lbs (1.8 kg) |
Combustible Gas Detector system eliminates the need for frequent response checks with ATi’s pioneering AutoTest. This transmitter performs an automatic test using self-generated gas on the sensing element every 24 hours with the world’s only self-testing AutoTest gas module for complete peace of mind, allowing for safer and more confident monitoring.
The A12-17 combustible gas sensors are made up of two matched sensing elements, one active and one passive. Both are electrically heated and form two legs of a Wheatstone bridge circuit. When combustible gas contacts the sensor, the active element catalyzes the oxidation of gas, heating the active element and changing its resistance. The passive element remains unchanged, resulting in a change in the bridge circuit that is proportional to the gas concentration. As long as the active element remains in good condition, the gas sensor will respond rapidly to the presence of combustible gas.
The Auto-Test gas sensor is a combination of a gas sensor and an electrochemical hydrogen gas generator integrated into an explosion-proof stainless steel housing. When activated by the electronic transmitter, the generator produces hydrogen that diffuses to the gas sensor through the flame arrestor protecting the sensor. If the gas sensor responds properly, the A12-17 Combustible Gas Transmitter will show a “Pass” indication. Should the sensor not respond properly, an “Auto Test Fail” message will activate at the gas transmitter and the 4-20 mA output from the transmitter will drop to 3 mA, providing for remote fault indication.
Combustible Gas Detectors are used in a wide variety of industrial plants to detect gas leakage or buildup before it reaches explosive levels. These detectors rely on thermal oxidation of any combustible gas or vapor on the surface of a heated catalyst. In other words, they simply burn the gas and measure the heat released in the combustion process.
While this type of sensor is generally stable and reliable, it is also subject to poisoning by silicon vapor, lead compounds, and other environmental contaminants. To detect loss of sensitivity, most users test combustible sensors either weekly or biweekly to ensure response. The procedure is simple, but requires manpower to perform the test.
ATI’s Auto-Test Combustible Gas Transmitter eliminates the need for frequent response checks. This transmitter performs an automatic gas test on the sensing element every 24 hours. The result is a combustible gas detector system with a level of reliability beyond that of any other system available. This daily sensor response verification is as close to a fail-safe detection system as you can find, with the added benefit of greatly reduced manual testing.
Combustible gas sensors are made up of two matched sensing elements, one active and one passive. Both are electrically heated and form two legs of a Wheatstone bridge circuit. When combustible gas contacts the sensor, the active element catalyzes the oxidation of gas, heating the active element and changing its resistance.
The passive element remains unchanged, resulting in a change in the bridge circuit that is proportional to the gas concentration. As long as the active element remains in good condition, the sensor will respond rapidly to the presence of combustible gas.
The Auto-Test sensor is actually a combination of a gas sensor and an electrochemical hydrogen gas generator integrated into an explosion-proof stainless steel housing.
When activated by the electronic transmitter, the generator produces hydrogen that diffuses to the gas sensor through the flame arrestor protecting the sensor. If the sensor responds properly, the combustible gas detector transmitter will show a “Pass” indication. Should the sensor not respond properly, an “Auto Test Fail” message will activate at the transmitter and the 4-20 mA output from the transmitter will drop to 3 mA, providing for remote fault indication.
Model A12-17 | – | DDD | – | E | – | F |
Code the measurement range using a 4-digit number. The standard range for a combustible gas system is 0-100% LEL, so the code is normally 0100. However, systems used for hydrogen are sometimes displayed in %, with a range of 0-4 percent (code 0004). If a range other than 0-100% LEL or 0-4% is required, consult factory for availability.
3 – %
4 – % LEL
1 – Sensor without Auto-Test
2 – Sensor with Auto-Test
3 – Remote sensor with junction box
4 – Remote sensor with junction box and Auto-Test
00-0261 Splash guard/remote calibration adapter for standard sensor
00-0258 Calibration adapter for standard sensor
45-0081 Splash guard for Auto-Test sensor (required for Auto-Test sensor)
Gas Type | Calibrated for methane unless otherwise specified |
Range | 0-100% LEL |
Response Time | (T90) 10 seconds |
Accuracy | Generally +5% of value, but limited by available calibration gas accuracy. |
Electronic Repeatability | +1% |
Electronic Linearity | +0.5% |
Zero Drift | Less than 2% full scale per month |
Span Drift | Less than 3% per month |
Output | Powered 4-20 mA, 1000 ohms max at 24 VDC |
Power | 12-30 VDC, 125 mA maximum |
Enclosure | Explosion-proof, Class 1, Div 1, Groups B,C, & D |
Sensor | 316 stainless steel |
Sensor Auto-Test | Hydrogen gas generator integral to gas sensor housing |
Control | 4 magnetic switches on front of transmitter |
Operating Temp | -40 ̊F to +70 ̊C |
Weight | 4lbs (1.8 kg) |